Commercial duty: peak draw-off is not continuous recovery

Read short-window capacity and sustained production together, with the starting store state and temperature rise kept visible.

Understand what each row buys you

A storage heater can deliver an initial reserve faster than its element can replace it. A peak-window draw-off figure therefore answers a different question from continuous litres per hour. Compare the same delivery temperature, inlet condition, starting store state and test duration before using either row.

The EES UK sheet makes the distinction explicit. For EES 30, with cold water at 10°C and the store set to its maximum temperature, the ΔT = 44°C rows give 147 litres over 30 minutes, 174 litres over 60 minutes and 201 litres over 90 minutes. The continuous row is 54 litres/hour under that temperature-rise condition.[1]

Dividing 147 litres by half an hour gives 294 litres/hour, but it would be wrong to call that the continuous rating. It annualises a short draw that benefits from the starting reserve. At ΔT = 50°C the same sheet instead lists 47 litres/hour continuously: conditions change the answer.[1]

Worked rejection check

Suppose a measured process needs 180 litres every hour at the same ΔT = 44°C basis, for several hours. That is 126 litres/hour more than the EES 30’s declared 54-litre/hour continuous production. An initial reserve can delay a shortfall; it cannot close that repeated hourly deficit. This is an illustrative comparison, not approval for a process application.

The EES sheet lists 3.0 kW input across its model range, despite increasing storage volume. Buying a bigger vessel in that range does not, by itself, increase the declared continuous row.[1] Do not add together the two listed elements to invent a 6 kW input.

Send a bounded duty brief

Ask the manufacturer or competent designer to assess repeated peaks, downtime and distribution against the actual application. Keep drinks demand separate from washwater and process demand: a boiling-drinks rating is not evidence for basin or equipment-washing capacity.

  • Log each peak’s litres, temperature, duration and simultaneous flow.
  • Declare the initial stored state and whether heat can recover between draws.
  • Include cleaning loads, distribution losses and the second and later peaks.
  • Obtain application confirmation and evidence at your conditions; do not extrapolate a maximum row into a service guarantee.